A pane of glass fell. What would it take to reopen the shopping centre?

A pane of glass fell. What would it take to reopen the shopping centre?

When glazing fell from its frame at a busy UK shopping centre, two FASET members helped the project team work out what evidence the engineers needed before the doors could reopen.

A large pane of glass fell from its frame at a busy UK shopping centre. Nobody was hurt. The centre closed temporarily, and the team faced an urgent question: if more glass fell, how would they protect the shoppers and staff below?

Two FASET members helped answer it.

Firstly, the shopping centre's engineers asked FASET member DTE Scaffolding and Safety Netting to install a safety net beneath the glazing, with a separate debris net to contain smaller fragments. DTE installed this as an urgent remedial action immediately after the fall.

The safety net conformed to BS EN 1263-1 which is used to catch falling persons. Conformity told the engineers about the net, but they needed further evidence about how the combined arrangement would perform in this application- particularly as the net was being asked to catch something other than a person.

Rob Harris, who represents 3 Education on the FASET board, advised on the netting and witnessed the test that followed.

Rob's suggestion was simple. "Why don't you test it?"

What did the engineers need to know?

Glass doesn't fall in one predictable way. A pane can come down flat, at an angle or edge-first. As Rob explained in conversation with FASET, the engineers first had to decide what evidence they needed to assess the proposed arrangement and how to create a test that evidence.

The test devised by the Engineer required the construction of a 5m tall test rig. It had a footprint of 7m x7m. DTE built this in their yard. The same rigger who had installed the netting at the shopping centre set up the test net. The team lowered a rigid, flat 150 kg plywood load into the net and held it there for three hours. Rob reported some movement as the net settled under the load, which was considered insignificant.

The test showed how the arrangement behaved under that specified sustained load. The engineers used the results as one part of their wider assessment of the remedial measures. Following their review, the shopping centre reopened with those measures in place.

What should facilities managers ask for?

If you're the person being asked when a building can reopen, "it's been tested" is the start of the conversation, not the end. Ask:

  • What did the test measure?
  • Why were those conditions chosen?
  • What did it not test, and how was that covered?
  • How did the engineers use the results to assess the risk at your building?

The same questions could come up at a school, another shopping centre or any public venue with overhead glazing.

A question for the industry

Existing standards don't always directly address the hazard in front of you. Could shared guidance from the glazing, netting and facilities management sectors help the next team decide what evidence it needs, faster?

FASET would like to hear from members, glazing specialists and facilities managers who have faced a similar decision. Email us at info@faset.org